ERFA Industries Group

ERFA Industries Group Xian ERFA Switchgear under ERFA Industries Group

Manufacturer from China
Active Member
7 Years
Home / Products / Vacuum Interrupter /

Industrial Vacuum Interrupter Used In Indoor Vacuum Type Circuit Breaker

Contact Now
ERFA Industries Group
Country/Region:china
Contact Person:MsLinda Dong
Contact Now

Industrial Vacuum Interrupter Used In Indoor Vacuum Type Circuit Breaker

Ask Latest Price
Place of Origin :China (Mainland)
Brand Name :ERFA
Certification :ISO9000
Model Number :ERFA-V24
MOQ :1 unit
Price :Negotiated
Packaging Details :each piece with polly then 18pcs in a woodenbox with pallet
Delivery Time :10 days after payment
Payment Terms :T/T
Supply Ability :10000pcs per month
Rated Current :1600A 1250A
Rated duration of short-circuit :4s
Rated peak withstand current :63ka
Storage life :20years
Contacts limit erosion :3mm
Rated operating sequence :O-0.3(0.5)S-CO-180S-CO
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Specification


1 Rated Current A 1600 1250
2 Circuit resistance at lowest rated contact force ≤25 ≤28
3 Rated short-circuit breaking current KA 25
4 Breaking operations of rated short circuit breaking current Times 20
5 Rated short-time withstand current KA 25
6 Rated duration of short-circuit S 4
7 Rated peak withstand current KA 63
8 Rated short -circuit making current KA 63
9 Rated breaking current of single capacitor bank A 630
10 Rated breaking current of back -to-back capacitor bank A 400
11 Rated operating sequence O-0.3(0.5)S-CO-180S-CO




Mechanical data

1 Weight of movable parts Kg 2.98
2 Closing force due to bellow and atmosphere N 170±40
3 Force required to hold contacts open at full stroke N 310±40





Mechanical requirements

1 Clearance between open contacts mm 22±2
2 Average opening speed(average of first 75% of contact gap) m/s 1.8±0.2
3 Average closing speed(average of last 30% contact gap) m/s 0.65±0.15
4 Rated added external contact final force N 3100±200
Added external contact force at contact touch point 2170±155
5 Contact bouncing duration at closing operation ms ≤3
6 Closing and opening non-simultaneity of three-phase contacts ms ≤2
7 Maximum rebound during opening mm ≤2




Life

1 Storage life Years 20
2 Mechanical endurance Times 10000
3 Contacts limit erosion Mm 3