Ask Latest Price
Place of Origin :China (Mainland)
Brand Name :ERFA
Certification :ISO9000
Model Number :ERFA-V12
MOQ :1 unit
Price :Negotiated
Packaging Details :each piece with polly then 18pcs in a woodenbox with pallet
Delivery Time :10 days after payment
Payment Terms :T/T
Supply Ability :10000pcs per month
Rated current :1600A 1250A
Rated duration of short-circuit :4S
Rated peak withstand current :60KA
Weight of movable parts :1.4KG
Contacts limit erosion :3MM
Certificate :ISO9000
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Specification

1 Rated current A 1600 1250
2 Circuit resistance at lowest rated contact force μΩ ≤20
3 Rated short-circuit breaking current KA 31.5
4 Breaking operations of rated short circuit breaking current Times 50
5 Rated short-time withstand current KA 31.5
6 Rated duration of short-circuit S 4
7 Rated peak withstand current KA 60
8 Rated short-circuit making current KA 60
9 Rated breaking current of single capacitor bank A 630
10 Rated breaking current of back-back capacitor bank A 400
11 Rated operating sequence O-0.3s-CO-180s-CO

Mechanical data

1 Weight of movable parts Kg 1.4
2 Closing force due to bellow and atmosphere N 140±50
3 Force required to hold contacts open at full stroke N 230±50

Mechanical requirements

1 Clearance between open contacts mm 11±1
2 Average opening speed(average of first 75% of contact gap) m/s 1.1±0.2
3 Average closing speed(average of last 30% of contact gap) m/s 0.6±0.2
4 Rated added external contact final force 3100±200
Added external contact force at contact touch point N 2200±150
5 Contact bouncing duration at closing operation ms ≤2
6 Closing and Opening non-simultaneity of three-phase contacts ms ≤2
7 Maximum Rebound during opening mm ≤2

Life

1 Storage life Years 20
2 Mechanical endurance Times 10000
3 Contacts limit erosion Mm 3

Inquiry Cart 0