16 KA Vacuum Fault Interrupter 10000 Times Mechanical Endurance 0.65KG

Ask Latest Price
Place of Origin :China (Mainland)
Brand Name :ERFA
Certification :ISO9000
Model Number :ERFA-V16
MOQ :1 unit
Price :Negotiated
Packaging Details :each piece with polly then 18pcs in a woodenbox with pallet
Delivery Time :10 days after payment
Payment Terms :T/T
Supply Ability :10000pcs per month
Rated Current :1250A
Rated Duration Of Short-circuit :4S
Rated Peak Withstand Current :40KA
Weight of movable parts :0.65KG
Contacts limit erosion :3MM
Storage life :20years
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description


Specification


1 Rated Current A 1250
2 Circuit resistance at lowest rated contact force ≤30
3 Rated short-circuit breaking current KA 16
4 Breaking operations of rated short circuit breaking current Times 30
5 Rated short-time withstand current KA 16
6 Rated duration of short-circuit S 4
7 Rated peak withstand current KA 40
8 Rated short -circuit making current KA 40
9 Rated breaking current of single capacitor bank A 400
10 Rated breaking current of back -to-back capacitor bank A 400
11 Rated operating sequence O-0.3(0.5)S-CO-180S-CO





Mechanical data

1 Weight of movable parts Kg 0.65
2 Closing force due to bellow and atmosphere N 80±40
3 Force required to hold contacts open at full stroke N 140±40





Mechanical requirements

1 Clearance between open contacts mm 16±1
2 Average opening speed(average of first 75% of contact gap) m/s 1.4±0.2
3 Average closing speed(average of last 30% contact gap) m/s 0.8±0.2
4 Rated added external contact final force N 2000±200
Added external contact force at contact touch point
5 Contact bouncing duration at closing operation ms
≤2
6 Closing and opening non-simultaneity of three-phase contacts ms
≤1
7 Maximum rebound during opening mm 2


Life

1 Storage life Years 20
2 Mechanical endurance Times 10000
3 Contacts limit erosion Mm 3